Guide to Basic Requirements of LED Emergency Lighting Fixtures
LED emergency lights are important daily lighting tools helping people escape and evacuate when emergency. Today Effort presents a guide to the basic requirements of LED emergency lighting fixtures.

 LED emergency lighting fixtures

 

Installation requirements for LED emergency lighting fixtures

1.Underground building lighting

Safety exit signs must be set up in accordance with the following requirements: the entrance and exit of each hall and room of the underground building need emergency lighting, the horizontal illumination of the ground should not be less than 0.5LX, the safety exit signs are best installed at the side of the evacuation exit and stairway above the height of more than 2 meters from the ground. Their evacuation routes should be located at intersections, corners, safety exits and stairwells for clear recognition. And evacuation marker lights should be placed at the top of the safety exit, stairway entrance, the corner is located roughly between 1-1.2 meters on the pavement, its spacing should not be greater than 10 meters, preferably using fluorescent lamps or incandescent lamps.

2.Backup lighting

Standby lighting is widely used, need to be placed in business halls, emergency rooms, duty rooms, power distribution rooms, restaurants, computer rooms, etc., where the distribution room, smoke machine room, fire control room and other installed standby lighting to maintain the normal lighting height, the other should also reach one tenth of the normal lighting, that is, important places need high brightness lighting, while unimportant places can be a little darker The operating room, emergency room and other medical guard cattle room equipment need security lighting, preferably using tungsten halogen lamps, can also be used to reliably ignite the fluorescent lamp.

3. The power supply of emergency lights

Another normal power supply or another power supply line can work normally in case of problems, or a generator independent of the power supply, or a battery can be used. These can be used as the power supply device for emergency lights.

 

The time requirement for emergency lights lighting to be put into conversion

Evacuation lighting should not be greater than 15 seconds, shopping malls and other places where the population is more concentrated should not be greater than 5 seconds, security lighting should not be greater than 0.5 seconds, the duration of the emergency lights should not be less than 30 minutes, and the room about the fire should not be less than 2 hours of continuous working time.

 

Emergency light control requirements

Standby and so on should be set circuit and switch control, the use of standby lights should be placed in emergency, to be normal lighting problems, standby lighting into use, usually not applicable evacuation control should be placed in the centralized room to deal with, or automatic control, not allowed to close the situation in place, emergency lights on the return can not be set socket. When choosing a battery should choose the function of automatic charging, emergency lights are strictly prohibited to use dimming devices.

 